Display & Keyboard | Process Value Display (PV) | 4 Digits, 7 segment red LED |
| Set value display (SV) | 4 digits 12.5mm, 7 segment yellow LED |
| Alarm 1 LED | 1 red LED |
| Mounting method | Suitable for Flush Panel Mounting |
| Ebat | Suitable for Flush Panel Mounting |
| Weight | Approx. 400 gram (after packing) |
| Electrical Characteristics |
| Supply | 230 Vac +10%-20%, 50/60Hz 9-30Vdc/7-24Vac ±%10 |
| Connection | 2.5 mm2'lik Socket Klemens |
| Scale | For Fe-Const (J) thermocouple 0...600 °C For NiCr-Ni (K) termocouple 0...1200 °C For Cu-Conts (T) termocouple 0...400 °C For Pt10Rh-Pt (S) termocouple 0...1600 °C For Pt13Th-Pt (R) termocouple 200...600 °C For Pt-100 resistance thermometer -200...600 °C For Pt-100 resistance thermometer -99.9...300.0 °C For 0-20mA ve 4...20mA 999...4000 |
| Accuracy | 0.2% full scale ±1 digit |
| Operation Temperature °C | 0...50 °C |
| Data Retention | EEPROM (minimum 10 years) |
| Control Output | 0-20mA, 4-20mA or logic output selectable |
| Control/Alarm2 Output | 1 Relay: 250Vac, 2A (resistive load), NO+NC |
| Alarm 1 Output | 1 Relay: 250 Vac, 2A (resistive load), NO+NC (selectable) |
| Control Algorithm | On-Off, P, PI, PD, PID (selectable) |
| Proportional Band | Adjustable between 0%and 100% |
| Integral Time | Adjustable between 0.00 and 25.00 min. |
| Derivative Time | Adjustable between 0.00 and 25 min. |
| Control Period | Adjustable between 1s and 250s |
| Hysteresis | Adjustable between 1 and 50 °C/°F |
| Output Power | The ratio of power at a set point can be adjusted between 0% and 100% |
|